RACKS / COOLING / POWER

Liquid cooling & CDU

Compare CDU30, CDU50, CDU100 and CDU300 specifications and pipework options. Share both coolant-loop conditions and equipment interfaces for project selection.

Final configuration, performance, applicable requirements and delivery are defined in the agreed project specification.

CDU30 / CDU50 / CDU100 / CDU300

Compare the four CDU models

Compare operating temperatures and both coolant circuits alongside cooling capacity to identify a suitable configuration.

Compare the four CDU models
Technical specificationsTBC-CDU30 ↗TBC-CDU50 ↗TBC-CDU100 ↗TBC-CDU300 ↗
Rated cooling capacity30 kW50 kW100 kW300 kW
Load-side circulation flow1–5 m³/h3–8 m³/h7–10 m³/h25–30 m³/h
Source-side circulation flow3–5 m³/h5–10 m³/h8–15 m³/h30–35 m³/h
Load-side supply / return40 / 50 °C40 / 50 °C40 / 50 °C40 / 50 °C
Source-side supply / return35 / 45 °C35 / 45 °C35 / 45 °C35 / 45 °C
Dimensions (W × D × H)600 × 1200 × 2200 mm600 × 1200 × 2200 mm600 × 1200 × 2200 mm600 × 1200 × 2200 mm

CDU300: the illustration shows several cabinets. Confirm whether the listed dimensions refer to one cabinet or the complete assembly.